company tower banner
Accepta Ltd Company Logo

Accepta® CG 364

1 of 30 products in this brand
Accepta® CG 364 is a chlorine stable, non-volatile liquid corrosion inhibitor and scale dispersant. It is an alkaline blend of anodic and cathodic inhibitors based on phosphate, a threshold deposit control agent, a sludge conditioner and offers protection to multi-metal systems.

Functions: Corrosion Inhibitor, Scale Inhibitor

Chemical Family: Phosphates

End Uses: Air Conditioning Plant, Cooling Towers

Applicable Processes: Sewage Treatment

Technical Data Sheet
  • TypeDocument Name
View All Documents

Knowde Enhanced TDS

Identification & Functionality

Chemical Family
Industrial Additives Functions

Features & Benefits

Labeling Claims
Product Features
  • Accepta® CG 364 contains no heavy metals.
  • It offers protection over a wide range of temperature conditions in low hardness and low alkalinity conditions.
  • Accepta® CG 364 is non-combustible

Applications & Uses

Markets
Applicable Processes
Industrial Additives End Use
Biocide Recommendations
  • For Bromine treatment we recommend: Accepta® 2343 & Accepta® Activator 120 together these will provide bromine in liquid form.
  • For Non-Oxidizing Biocide treatment we recommend: Accepta® 2827 & Accepta® 2302 dosed alternatively these non-oxidizing biocides will maintain excellent control.
Product Applications
  • Accepta CG364 contains no heavy metals. It offers protection over a wide range of temperature conditions in low hardness and low alkalinity conditions.
  • Treatment for open circuit evaporative cooling systems and air conditioning plant
  • Accepta® CG 364 has an extended range of water chemistry where the product can be used as the potential for calcium phosphate deposition is minimized.
  • The product is most commonly used as an inhibitor in pasteurization systems where the combination of high temperatures and high chlorine levels proves extremely aggressive. To perform satisfactorily CG365 requires low levels of Calcium Hardness present (20-200mg/l)
  • Accepta® CG 364 is suitable for use with bromine based biocides and a regime of alternating non-oxidizing biocides.
Dosage Rates Information
  • To ensure rapid film formation and corrosion control the system should be passivated for a period of at least one week with 500ppm Accepta® CG 364 in the system water.
  • Accepta® CG 364 should be dosed to maintain a reserve of 100 - 200ppm in the system water. For maximum control and economy it should be dosed in proportion to make-up requirements.

Properties

Physical Form
Appearance
Clear liquid
Odor
Characteristic
Soluble in
Water
Typical Properties
ValueUnitsTest Method / Conditions
Relative Density1.25 - 1.30--
pH11 - 12--

Packaging & Availability

Packaging
  • WeightL: 25 kg