company tower banner
Carus Group Company Logo

CARUSOL® LIQUID PERMANGANATE

1 of 1 products in this brand
CARUSOL® LIQUID PERMANGANATE is an effective oxidant recommended for potable drinking water applications that require a concentrated permanganate solution. Applications include iron and manganese reduction, taste and odor control, disinfection by-product reduction, color reduction, and radium reduction.

Chemical Name: Sodium Permanganate

Technical Data Sheet
  • TypeDocument Name
View All Documents

Knowde Enhanced TDS

Identification & Functionality

Chemical Family
Chemical Name
Molecular formula
NaMnO4
CAS No.
10101-50-5
EC No.
233-251-1

Features & Benefits

Benefits
  • Concentrated liquid oxidant
  • More precise dosing of chemical
  • Feed equipment is simplified
  • Consistent concentration

Applications & Uses

Markets
Applicable Processes
Base Chemicals End Uses
Applications
  • Drinking Water Purification
  • Iron/Manganese Oxidation
  • Taste and Odor Control
  • Preoxidant for THM and HAA Control
  • Hydrogen Sulfide Control
  • Radium Removal
  • Color Removal

Properties

Physical Form
Appearance
Dark Purple Solution
Miscible in
Water
Typical Properties
ValueUnitsTest Method / Conditions
Assay (NaMnO₄)19.5 - 21.5%-
pH5.0 - 8.0EP
Specific Gravity1.15 - 1.17--
Freezing Point-6.0°C-

Regulatory & Compliance

Standards and Specifications

CARUSOL meets:

  • AWWA Standard B603-10
  • EN: 15482 - 10 mg/L max
  • ANSI/NSF 60
  • KIWA- Product certification no. K83927 - 17 mg/L max
  • NSF Maximum Use Level 176 mg/L

Technical Details & Test Data

Compatibility Information

CARUSOL liquid permanganate is compatible with many metals and synthetic materials. Natural rubbers and fibers are often incompatible. Solution pH and temperature are also important factors. The material selected for use with liquid permanganate must also be compatible with any kind of acid or alkali being used. In neutral and alkaline solutions, sodium permanganate is not corrosive to carbon steel and 316 stainless steel; however, chloride corrosion of metals may be accelerated when an oxidant such as liquid permanganate is present in solution. Plastics such as Teflon, polypropylene, and HDPE are also compatible with liquid permanganate.

Aluminum, zinc, copper, lead, and alloys containing these metals may be (slightly) affected by sodium permanganate solutions. Actual corrosion or compatibility studies should be made under the conditions in which permanganate will be used prior to use.

Packaging & Availability

Shipping Containers
  1. 5-gallon (20-L) Jerrican - (UN Specification: UN3H1/Y1.8/100) Made of high density polyethylene (HDPE). Weighs 3.3 lb (1.5 kg). The net weight is 48.5 lb (22 kg). The jerrican stands approximately 13.4 in. tall, 9.4 in. wide, and 13.0 in. deep (33.9 cm high, 23.8 cm wide, and 33.0 cm. deep).
  2. 55-gallon (208.2L) - Closed Head HDPE Drum (UN Specifications: UN1H1/Y1.9/100) Made of high density polyethylene (HDPE). Weighs 20.5 lb (9.3kg). The net weight is 533.5 lb (241.9 kg). The drum stands approximately 35.1 in. tall and has an outside diameter of 23.4 in. (89.1 cm tall, OD 59.4 cm).
  3. 275-gallon (1041 L) IBC (Intermediate Bulk Container) - (UN Specification: UN31HA1/Y1.9/100) They are also marked “MX” for multi-trip IBC. Weighs 123 lb (55.8 kg). The net weight is 2550 lb (1160 kg). The IBC contains 263 gallons of product. The IBC dimensions are 45.3 in. (114.9 cm) high, 47.3 in. (120.0 cm) long, and 39.4 in. (100.0 cm) wide. The IBC has a 2 in. butterfly valve with NPT threads in bottom sump.
  4. Bulk Shipping Quantities from 3000-4200 gallons are available.
Shipping

CARUSOL® liquid permanganate is classified and listed as an oxidizer by PHMSA (Pipeline and Hazardous Materials Safety Administration, Department of Transportation, in 49 CFR Subchapter C, HMR (Hazardous Materials Regulation), Part 172.101 HMT (Hazardous Materials Table).

  1. Proper Shipping Name: Permanganates, inorganics, aqueous solution n.o.s. (Contains sodium permanganate).
  2. Hazard Class: 5.1
  3. Identification Number: UN 3214
  4. Packaging Group: II
  5. Label Requirements: Oxidizer, 5.1
  6. Packaging Requirements: 49 CFR Parts 171 to 180
  7. Sections: 173.152, 173.202, 173.242

Storage & Handling

Handling, Storage, and Incompatibility

Like any strong oxidant, CARUSOL liquid permanganate should be handled with care. Protective equipment during handling should include face shields and/or goggles, rubber or plastic gloves, and rubber or plastic apron. If clothing becomes spotted, wash off immediately; spontaneous ignition can occur with cloth or paper. In cases where significant exposure exists, use of the appropriate NIOSH-MSHA dust or mist respirator is recommended.

Store in accordance with NFPA (National Fire Protection Association) Code 430 requirements for Class II Oxidizers. The product should be stored in a cool, dry area in closed containers. Concrete floors are preferred. Avoid wooden decks. Spillage should be collected and disposed of properly. Contain and dilute spillage to approximately 6% with water, and then reduce with sodium thiosulfate, a bisulfite, or ferrous salt solution. The bisulfite or ferrous salt may require some dilute sulfuric acid (10% w/w) to promote reduction. Neutralize with sodium carbonate to neutral pH, if acid was used. Deposit sludge in an approved landfill or, where permitted, drain into sewer with large quantities of water.

As an oxidant, the product itself is non-combustible, but will accelerate the burning of combustible materials. Therefore, contact with all combustible materials and/or chemicals must be avoided. These include but are not limited to: wood, cloth, organic chemicals, and charcoal. Avoid contact with acids, peroxides, sulfites, oxalates, and all other oxidizable inorganic chemicals. During contact with hydrochloric acid, chlorine is liberated.