Base: Water
Chemical Family: Synthetic Latex
Features & Benefits
- Labeling Claims
- Ready-to-Use Product Features
- Features & Benefits
- LEED V4 Qualified
- UL Classified
- Low VOC
- NFPA 90A & 90B
- Encapsulant
- Excellent Flexibility
- Non-Flammable Wet and Dry
- Smooth Finish
- Prevents Fiber Erosion
- Durable
- Excellent Water and U.V. Resistance
Applications & Uses
- Applications
- Application Area
- Compatible Substrates & Surfaces
- Recommended Uses
- May be used to coat the interior of lined residential and commercial HVAC air ducts and plenums.
- May be used to protect line set insulation from harmful UV exposure (DP 2515-White).
- May be used in shop or field applications on faced or unfaced fiberglass duct liner insulation and fiberglass duct board to act as an effective control of fiberglass erosion.
- May be used to repair damaged mechanical insulation.
- Directions for Use
Surface Preparation: Surfaces should be clean, dry and free of dirt, oil, and any foreign matter.
Application: May be applied by brush, roller, or airless sprayer. Apply at a rate of 75 sq. ft. per gallon. Spray gun application should coat surface thoroughly and evenly with one application; apply second coat to porous or irregular surfaces. Brush or roller application requires two coats applied at 90 degrees. HVAC systems should be under negative air pressure during applicaton. Circulate fresh air through the system to dry coating. Air should be odorless and filters replaced before venting into occupied areas. For interior HVAC fiberglass edge coating applications, brush or spray 2510 - Black Duct Liner And Line Set Protective Coating into cut edges of fiberglass. Apply sufficient product to thoroughly coat all exposed fiberglass. Where possible, coated edges should face downstream. Apply metal nosing as required by SMACNA.
Do not thin.
Properties
- Color
- Typical Properties
Value | Units | Test Method / Conditions | |
Application Temperature | 40 - 110 | °F | — |
Coverage (Dependent on Application Thickness, 20-40 Wet Miils) | 75.0 | sq. ft. | — |
Cure Time | 4 - 16 | Hour | — |
Flammability | Non-flammable Wet or Dry | — | — |
Flash Point | No Flash to Boiling | °F | — |
Freeze/Thaw Stability | Do not allow to freeze | — | — |
Service Temperature | -25 to 200 | °F | — |
Solids Content | 56 - 60 | % | — |
Storage Temperature | 40 - 110 | °F | — |
Viscosity | 4000 - 5000 | Cps | — |
VOC | 2.0 | g/l | — |