Knowde Enhanced TDS
Identification & Functionality
- Product Type
- Technologies
- Product Families
Features & Benefits
- Ready-to-Use Product Features
Applications & Uses
- Compatible Substrates & Surfaces
- Surface preparation
Wood and Combustible Surfaces: New wood, fiberboard and other surfaces having uneven or excessive porosity should be scaled with Flame Control 3001 Aeryhe Promer and allowed lo dry a minimum of 16 hours belore applying BURN BARRIER™ NO. 30-30 Semi-Gloss Enamel.
Noncombustible Surfaces: Dirt, grease, oil, and other foreign matter must be removed. Dull all glossy surfaces.
- Application
Stir well before using. Can be brush, spray or roller applied. If applied by spray, heavy-duty spray equipment is recommended. Thinning is not recommended; however, if desired for spray application, use only Burn Barrier™ Reducer for No. 30-30 or Odorless Mineral Spirits.
- Suggested Coverage Rate
400 sq.ft./U.S. gallon [9.82 m²/L] in one or two coats.
- Drying Time
- Dries to touch: 2 - 4 hours (25°C, 50%RH)
- Tack free: 5 - 8 hours (25°C, 50%RH)
- Through dry: 3 - 4 days (25°C, 50%RH)
Allow at least 24 hours of drying time before recoating.
- Thinners
For thinning and cleaning equipment, use Burn Barrier™ Special Reducer for No. 30-30 or odorless mineral spirits.
Technical Details & Test Data
- Test Data
Coating System Details Classification/rating (When Applied to Douglas Fir) Flame Spread (ASTM E-84) Smoke Spread (ASTM E-84) Primer None 5 20 Base Coat Type 30-30A applied in one coat at 400 sq. ft./U.S. gal. (9.82 m²/L) Top Coat None
Safety & Health
- Caution
The liquid coating contains Mineral Spirits. Due care must be exercised during and after application until the coating is dry. Keep away from heat, sparks, and flame. Avoid contact with skin. Avoid breathing vapors or spray mist. Open windows and doors or use other means to ensure fresh air entry during application and drying. If you experience eye watering, headaches or dizziness, increase fresh air or wear respiratory protection (NIOSH/MSHA TC 23C or equivalent) or leave the area. Do not take it internally. Close container after each use. Use with adequate ventilation.
Packaging & Availability
- Tinting
Available in white, off white, and pastel shades or may be field tinted with most universal or oil tinting colorants. Tinting colorants should not exceed 4 fluid ounces per gallon.
- Packaging
Standard packaging:
- 1 gallon cans
- 5 gallon pails
- 55 gallon drums