company tower banner
Pluss Advanced Technologies Pvt Ltd Company Logo
savE® FS21R is form stable phase change material, liquid PCM embedded in polymer matrix.

Functions: Phase Change Material (PCM)

Applicable Processes: HVAC Application

Features: Cost Effective, Long Shelf Life

Technical Data Sheet
  • TypeDocument Name
View All Documents

Knowde Enhanced TDS

Identification & Functionality

Industrial Additives Functions

Features & Benefits

Industrial Additives Features

Applications & Uses

Applicable Processes

Properties

Appearance
Black solid (at 25°C)
Typical Properties
ValueUnitsTest Method / Conditions
Phase Transition Temperature (Melting at 31°C air bath)19°CPLUSS® T-History
Phase Transition Temperature (Freezing at 11°C air bath)21°CPLUSS® T-History
Density Liquid (at 30°C)898kg/m³ASTM D891-95
Density Solid (at 0°C)887kg/m³ASTM D891-95
Number of Cycles Testedaprrox. 2000PLUSS® Internal
FlammabilityYes
Flash Point160°C
Thermal Properties
ValueUnitsTest Method / Conditions
Latent Heat Enthalpy (Melting at 16 to 26 °C)170kJ/kgPLUSS® T-History
Latent Heat Enthalpy (Freezing at 26 to 16°C)121kJ/kgPLUSS® T-History
Specific Heat (liquid at 30°C)2.68kJ/kgKPLUSS® T-History
Specific Heat (solid at 10°C)2.56kJ/kgKPLUSS® T-History
Thermal Conductivity (liquid at 40°C)0.1W/mKKD2Pro
Thermal Conductivity (solid at 5°C)0.3W/mKKD2Pro
Maximum Operating Temperature90°C
Note

* Determined by T-history.

** Nominal Valu[es. Actual values mentioned in test certificate.

Technical Details & Test Data

Test Data

 

Phase transition temperature range and stored thermal energy*

savE® FS21R - Test DataTemperature vs time curve

savE® FS21R - Test Data - 1Enthalpy vs temperature curve