savE® HS10N is an inorganic phase change material.

Functions: Phase Change Material (PCM)

Chemical Family: Hydrated Salts

Applicable Processes: HVAC Application

Features: Cost Effective, Long Shelf Life

Technical Data Sheet
  • TypeDocument Name
View All Documents

Knowde Enhanced TDS

Identification & Functionality

Chemical Family
Industrial Additives Functions

Features & Benefits

Industrial Additives Features

Applications & Uses

Applicable Processes

Properties

Appearance
Off-white liquid/grey colored liquid (at 25°C)
Typical Properties
ValueUnitsTest Method / Conditions
Phase Transition Temperature (Melting at 0°C liquid bath)-10°CPLUSS® T-History
Phase Transition Temperature (Freezing at -20°C liquid bath)-11°CPLUSS® T-History
Nucleation Temperature (at -20°C liquid bath)-11°CPLUSS® T-History
Density Liquid (at 30°C)1125kg/m³ASTM D891-95
Density Solid (at -20°C)1057kg/m³ASTM D891-95
Number of Cycles Testedaprrox. 2000PLUSS® Internal
FlammabilityNo
Thermal Properties
ValueUnitsTest Method / Conditions
Latent Heat Enthalpy (Melting at -15 to -5 °C)330kJ/kgPLUSS® T-History
Latent Heat Enthalpy (Freezing at -5 to -15°C)333kJ/kgPLUSS® T-History
Specific Heat (liquid at 30°C)3.4kJ/kgKPLUSS® T-History
Specific Heat (solid at -12°C)1.9kJ/kgKPLUSS® T-History
Thermal Conductivity (liquid at 30°C)0.6W/mKKD2Pro
Thermal Conductivity (solid at -12°C)4.25W/mKKD2Pro
Maximum Operating Temperature90°C
Note

* Determined by T-history.

** Nominal Valu[es. Actual values mentioned in test certificate.

Technical Details & Test Data

Test Data

Phase transition temperature range and stored thermal energy*

savE® HS10N - Test Data

Temperature vs time curve

savE® HS10N - Test Data - 1

Enthalpy vs temperature curve