company tower banner
Pluss Advanced Technologies Pvt Ltd Company Logo
savE® HS22 is an inorganic phase change material.

Functions: Phase Change Material (PCM)

Chemical Family: Hydrated Salts

Applicable Processes: HVAC Application

Features: Cost Effective, Long Shelf Life

Technical Data Sheet
  • TypeDocument Name
View All Documents

Knowde Enhanced TDS

Identification & Functionality

Chemical Family
Industrial Additives Functions

Features & Benefits

Industrial Additives Features

Applications & Uses

Applicable Processes

Properties

Appearance
Bluish liquid with white sediment (at 25°C)
Typical Properties
ValueUnitsTest Method / Conditions
Phase Transition Temperature (Melting at 32°C liquid bath)23°CPLUSS® T-History
Phase Transition Temperature (Freezing at 12°C liquid bath)22°CPLUSS® T-History
Nucleation Temperature (at 12 °C liquid bath)21°CPLUSS® T-History
Density Liquid (at 30°C)1540kg/m³ASTM D891-95
Density Solid (at 0°C)1651kg/m³ASTM D891-95
Number of Cycles Testedaprrox. 2000PLUSS® Internal
FlammabilityNo
Thermal Properties
ValueUnitsTest Method / Conditions
Latent Heat Enthalpy (Melting at 18 to 28 °C)190kJ/kgPLUSS® T-History
Latent Heat Enthalpy (Freezing at 28 to 18°C)162kJ/kgPLUSS® T-History
Specific Heat (liquid at 31°C)2.53kJ/kgKPLUSS® T-History
Specific Heat (solid at 0°C)2.27kJ/kgKPLUSS® T-History
Thermal Conductivity (liquid at 30 C)0.56W/mKKD2Pro
Thermal Conductivity (solid at 15°C)1.13W/mKKD2Pro
Maximum Operating Temperature90°C
Note

* Determined by T-history.

** Nominal Valu[es. Actual values mentioned in test certificate.

Technical Details & Test Data

Test Data

Phase transition temperature range and stored thermal energy*

savE® HS22 - Test DataTemperature vs time curve

savE® HS22 - Test Data - 1Enthalpy vs temperature curve