company tower banner
Pluss Advanced Technologies Pvt Ltd Company Logo
savE® HS3N is an inorganic phase change material.

Functions: Phase Change Material (PCM)

Chemical Family: Hydrated Salts

Applicable Processes: HVAC Application

Features: Cost Effective, Long Shelf Life

Technical Data Sheet
  • TypeDocument Name
View All Documents

Knowde Enhanced TDS

Identification & Functionality

Chemical Family
Industrial Additives Functions

Features & Benefits

Industrial Additives Features

Applications & Uses

Applicable Processes

Properties

Appearance
Transparent liquid (at 25°C)
Typical Properties
ValueUnitsTest Method / Conditions
Phase Transition Temperature (Melting at 10°C liquid bath)-2°CPLUSS® T-History
Phase Transition Temperature (Freezing at -13°C liquid bath)-3°CPLUSS® T-History
Nucleation Temperature (at -13 °C liquid bath)-5°CPLUSS® T-History
Density Liquid (at -20°C)1060kg/m³ASTM D891-95
Density Solid (at 30°C)985kg/m³ASTM D891-95
Number of Cycles Testedaprrox. 1000PLUSS® Internal
FlammabilityNo
Thermal Properties
ValueUnitsTest Method / Conditions
Latent Heat Enthalpy (Melting at -7 to 3 °C)359kJ/kgPLUSS® T-History
Latent Heat Enthalpy (Freezing at 3 to -7°C)329kJ/kgPLUSS® T-History
Specific Heat (liquid at 30°C)3.98kJ/kgKPLUSS® T-History
Specific Heat (solid at -10°C)1.8kJ/kgKPLUSS® T-History
Thermal Conductivity (liquid at 30°C)0.35W/mKKD2Pro
Thermal Conductivity (solid at -11°C)2.2W/mKKD2Pro
Maximum Operating Temperature80°C
Note

* Determined by T-history.

** Nominal Valu[es. Actual values mentioned in test certificate.

Technical Details & Test Data

Test Data

Phase transition temperature range and stored thermal energy*

savE® HS3N - Test Data

Temperature vs time curve

savE® HS3N - Test Data - 1Enthalpy vs temperature curve