- Features
- Fire rated
- Permanently flexible
- Water-based
- 0 slump (ASTM D2202)
- VOC Compliant
- Excellent Adhesion
Applications & Uses
- Applications
- Application Area
- Compatible Substrates & Surfaces
- Recommended Uses
Fireseal™ 814 has been tested where services penetrate through concrete walls, floors, and drywall construction, and is suitable for use around copper and steel pipes, steel conduits, electrical cables, data and telephone cables, PVC, CPVC pipes, and HVAC ducts.
- Application Instructions
- Areas to be sealed must be dry, clean and free from oil, grease and foreign matter
- Verify that any annular space between the through-penetration and the opening is within the limits defined by the tested constructions
- When mineral wool is required, cut oversize and pack tightly into space between the opening and the service, ensuring that the forming is positioned to allow for correct depth of FIRESEAL 814 sealant (contingent upon system design)
- Apply FIRESEAL 814 using a conventional caulking gun, pneumatic gun, putty knife or trowel
- When desired depth of FIRESEAL 814 sealant has been achieved, smooth surface with damp knife or spatula
- Clean Up
Use warm soapy water (when wet).
- Coverage Rate
10.3 oz. tube: 31 linear ft. 3/16" bead
- Temperature Limits
Application: 35° - 110°F
Service: -4°F - 158°F
Storage: 40°F - 86ºF
- Paintability
- Latex - When Cured
- Oil Base - When Cured
Properties
- Typical Properties
Value | Units | Test Method / Conditions | |
Tack Free Time (77º, 50% RH) | 1.0 | h | — |
Curing Time (77ºF, 1/4" bead) | 48.0 | h | — |
Flame Spread (Class 1 Smoke and Flame Rating) | 10.0 | — | UL 723, ASTM E-84, NFPA 90A, 90B and 225 |
Smoke Developed (Class 1 Smoke and Flame Rating) | 0.0 | — | UL 723, ASTM E-84, NFPA 90A, 90B and 225 |
VOC | 133.0 | g/l | — |
Weight (Per Gallon) | 13.4 - 14.0 | lbs | — |
Solid Content | 78 - 82 | % by Weight | — |
Regulatory & Compliance
- Certifications & Compliance
- Specification Approvals
Tested in accordance with ASTM E-814, UL 1479. UL Classified 1 and 2 Hour Rating.
Safety & Health
- Safety Precautions
First Aid: For skin contact, wash skin thoroughly with soap and water. For eye contact, irrigate with clean fresh water for at least 10 minutes holding eyelids apart, and seek medical advice. If swallowed, wash mouth with water and give water to drink. Do not induce vomiting. Keep out of reach of childeren.
Packaging & Availability
- Packaging
12 - 10.3 oz Tubes Per Case / 45 Cases Per Pallet / 540 Tubes
Storage & Handling
- Shelf Life
12 months in unopened containers.