company tower banner
Accepta Ltd Company Logo

Accepta® CG815

1 of 30 products in this brand
Accepta® CG815 is a chlorine stable, non volatile liquid corrosion inhibitor and scale dispersant, for use in open evaporative cooling systems. It is an alkaline blend of corrosion inhibitor, a threshold deposit controller and sludge conditioner offering protection to multi-metal systems without the requirement of additional specific corrosion inhibitors.

Functions: Corrosion Inhibitor, Scale Inhibitor, Sludge Conditioning Agent

End Uses: Cooling Towers

Applicable Processes: Cooling Water Treatment

Technical Data Sheet
  • TypeDocument Name
View All Documents

Knowde Enhanced TDS

Identification & Functionality

Features & Benefits

Labeling Claims
Product Benefits
  • ACCEPTA CG815 contains no controversial constituents such as heavy metals or phosphates, whose use is becoming increasingly restricted.
  • It offers protection over an extended range of pH, temperature and raw water hardness.

Applications & Uses

Markets
Applicable Processes
Industrial Additives End Use
Product Applications
  • Treatment for open evaporative cooling systems
  • Ideal treatment for both building services and industrial application.
Dosage Rates Information
  • To ensure rapid film formation and corrosion control the system should be pre-treated with Accepta® CG815 for two or three weeks at twice the normal continuous dosage.
  • Accepta® CG815 should be dosed to maintain a reserve of 50ml/m³ in recirculation.
  • For maximum control and economy it should be dosed continuously, best results will usually achieved by employing an automatic proportional dosing unit.

Properties

Physical Form
Odor
Characteristic ammonia
Soluble in
Water
Typical Properties
ValueUnitsTest Method / Conditions
Relative Density1.30 - 1.40--
pH12 - 13--