- Recommended Sprayer
Pump Wagner PS 3.34 PSI 3,300 GPM 1 Tip 517 - 523 or equivalent. Filter 60 mesh at machine Hose 3/8" diameter airless spray line for the first 100" from pump and 1/4" x3" whip Pump (Graco) TexSpray Mark 5 or equivalent PSI 3,300 GPM 1.35 Tip 517 - 523 or equivalent. Filter 60 mesh at the machine, removal of filter is recommended from gun Hose 3/8" diameter airless spray line for the first 100" from pump and 1/4" x3" whip - Installation Guide
- Surfaces to be coated must be clean and dry.
- Use a dry rag to remove any oil, grease, and dirt before cable coating application.
- Mix DC310 cable coating thoroughly with a power agitator before application.
- Thinner is normally not required.
- If necessary, use potable water (3% max.) to adjust viscosity.
- Water is also used for tools and spray machine cleaning.
- Coating can be applied using airless spray equipment in a single pass, not more than 1 - 1.2 mm (wet coating thickness) to prevent slumping.
- Surface shall be measured using a wet film thickness gage.
- If applying coating by brush or roller, it may be required to apply thinner coats to prevent slumping.
- The coating should be applied when the site temperature is between 5°C and 40°C and with less than 80% relative humidity.
- Temperature must be maintained until coating has fully dried.
- Verify the DFT by using calipers to measure the cable before coating and once the coating has fully dried.
- Do not allow the coating material to remain in hoses, guns or spray equipment.
- Clean all equipment with water immediately after use.
- All unused coating should be stored in a tightly closed container.
- Surface skinning may show in a partially filled container.
- Filter the material before use.
- Uses
- Cable bundle
- Cable tray
Properties
- Specifications
Value | Units | Test Method / Conditions | |
Density | 1.2 - 1.4 | kg/L | — |
Viscosity (25°C, Adjustable) | 10000 - 25000 | cPs | — |
pH Value | 7 - 8 | — | — |
VOC | 56.0 | °F | — |
Typical Thickness (WFT equivalent to 0.6mm DFT) | 1.0 | mm | — |
Solids by Volume | min. 60 | % | — |
Drying Time (25°C, Touch Dry) | 3 - 4 | hours | — |
Drying Time (25°C, Dried Through) | 24.0 | hours | — |
Application Temperature | 40 - 86 | °F | — |
In-Service Temperature | -4 to 158 | °F | — |
Relative Humidity | max. 80 | % | — |
Regulatory & Compliance
- Certifications & Compliance
Technical Details & Test Data
- Testing
- IEEE383: Standard for Qualifying Electric Cables and Splices for Nuclear Facilities.
- IEC60332-3A: Test of vertical flame spread on single or grouped electrical cables.
- IEEC60331-11: Tests for Electric Cables under Fire Conditions - Circuit Integrity.
- IEC60331-21: Tests for Electric Cables under Fire Conditions - Circuit Integrity.
- UL1709: Rapid Rise Hydrocarbon Fire Curve.
- GB28374: Standard flame spread test of electrical cables.
- ASTM D5116: Determination of Organic Emissions from Indoor Materials/Products.
- ASTM E662: Standard Test Method for Specific Optical Density of Smoke Generated by Solid Materials.
Packaging & Availability
- Packaging
- 25Kgs/Pail
Storage & Handling
- Storage Temperature
- 40 - 95 °F
- Shelf Life
- 12 months