International Fireproof Technology Company Logo

International Fireproof Technology INSS1440 Fire Barrier Caulk

INSS1440 Fire Barrier Caulk is a single component water-based acrylic intumescent firestop sealant. INSS1440 Listed designs the useless product and offers exceptional performance, making it more cost-effective than other traditional firestop caulkings. The product’s fast expansion technology quickly fills voids, offering excellent protection from fire, heat transfer, smoke and gasses.

Product Type: 1K (1 component) Sealant, Intumescent Sealant, Waterborne Sealant

Application Area: Pipes, Window Frames

Application Method: Gun, Trowel

Chemical Family: Acrylics & Acrylates

  • TypeDocument Name
View All Documents

Knowde Enhanced TDS

Identification & Functionality

Chemical Family

Features & Benefits

Applications & Uses

Application Area
Application Method
Uses
  • INSS1440 is used for sealing gaps around single or multiple penetrations through interior walls and floors, or for sealing gaps around doors and window frames in critically fire-rated structures.
  • INSS1440 Fire Barrier Caulk will adhere to most construction materials and penetrant items, is installation-friendly, asbestos and halogen-free, and can be painted after full curing.
Installation Guide
  • Ensure the application area is clean and free of oil, loose dirt, rust or scale and is dry and frost-free.
  • Install the correct depth and compression of backing material, if required, as detailed within the applicable listed system, allowing for sufficient depth of fill material.
  • Using a caulking gun, trowel or putty knife, apply INSS1440 fire barrier caulk into the seams, gaps or voids between forming material and floor or wall surface.
  • Tool the sealant surface smooth using a putty knife dipped in water, making complete contact with substrates to ensure an air and smoke tight seal.
  • Clean up, as necessary, with water.
  • INSS1440 fire barrier caulk cures by water evaporation and is not recommended for use in a wet environment.
Types of Applications
  • No penetration
  • Metallic pipe
  • Air duct
  • Busway
  • Plastic pipe
  • Cable bundle
  • Cable tray
  • Insulated pipe
  • Multiple penetration
  • Joint systems
  • Drywall

Properties

Specifications
ValueUnitsTest Method / Conditions
Specific Density1.4 - 1.6g/cm³
VOC23.0g/L
STC64.0
Tack Free time30.0minutes
Curing time7 - 21days
Expansion rate3 - 5
Application Temperature40 - 104°F
In-Service Temperature-13 to 176°F

Regulatory & Compliance

Certifications & Compliance

Technical Details & Test Data

Testing
  • ASTM E814 up to 3 hr F&T Rating
  • UL 1479 up to 3 hr F&T Rating
  • L Rating at Ambient - Less than 1 cfm/sq. ft.
  • ULC S-115 up to 3 hr F Rating
  • Up to 2 hr FT Rating
  • Up to 3 hr FH Rating
  • Up to 2 hr FTH Rating
  • L Rating at Ambient - Less than 5.1 L/S/m2
  • FM Approved
  • CNS 14514 up to 3 hr Class A&B
  • GB 23864
  • ASTM E84 - Flame 5 Smoke 20
  • ASTM E662 & FAR 25.853
Performance

50+ years HOAC tested.

Packaging & Availability

Packaging
  • 310 ml/Tube
  • 25 Tubes/CTN
  • 20 fl. oz./Sausage
  • 20 Sausages/CTN
  • 1 gal/pail & 5 gal/pail

Storage & Handling

Storage Temperature
50 - 95 °F
Shelf Life
24 months